Senin, 22 Februari 2016

KYORITSU Analogue Insulation / Continuity Tester MODEL 3132A

Analogue Insulation / Continuity Tester

MODEL3132A
 
Selection GuideProduct Catalogue
 

Dust and drip proof construction. (designed to IEC 60529 IP54)
Designed to meet IEC 61010-1 and IEC 61557 safety standard.
1mA rated test current at the minimum resistance.
200mA measuring current on continuity testing.
Automatic discharge of circuit capacitance.
(Any charge stored in the circuit under test will be automatically discharged after testing.)
Live circuit warning buzzer and neon lamp.
Small and lightweight. Shock resistant new case material.
AC voltmeter with linear, easy-to-read scale.
Operates on AA, R6 × 6 dry batteries.

3132A
CE
 
Insulation Resistance
Test Voltage250V/500V/1000V
Measuring Ranges
(Mid-scale Value)
100MΩ/200MΩ/400MΩ
(1MΩ) (2MΩ) (4MΩ)
Output Voltage
on open circuit
Rated test voltage+20%, -0%
Nominal Current1mA DC min.
Output Short
Circuit Current
1 - 2mA DC
Accuracy0.1 - 10MΩ/0.2 - 20MΩ/0.4 - 40MΩ
(Accuracy Guaranteed Ranges) ±5% of indicated value
Continuity
Measuring Ranges
(Mid-scale Value)
3Ω/500Ω
(1.5Ω) / (20Ω)
Output Voltage
on open circuit
4.1V DC approx.
Measuring Current210mA DC min.
Accuracy|±1.5% of scale length
AC Voltage
AC Voltage0 - 600V AC
Accuracy|±5% of scale length
General
Safety StandardIEC 61010-1 CAT III 600V Pollution Degree 2
IEC 61010-2-031
IEC 61557-1/2/4
IP RatingIEC 60529-IP54
EMC StandardIEC 61326-1
Withstand Voltage3700V AC for 1 minute
Power SourceR6 (AA) (1.5V) × 6
Dimensions106(L) × 160(W) × 72(D)mm
Weight560g approx.
Accessories7122B (Test leads) Pouch for test leads
8923 (F500mA/600V fuse) × 2
R6 (AA) × 6
Shoulder Strap
Instruction Manual

Tidak ada komentar: