KYORITSU Leakage Clamp Meters KEW 2413F

Leakage Clamp Meters

KEW2413F
 
Selection GuideInstruction Manual
 

Extra wide transformer jaws are best suited for clamping on all three or four wires (3phases) together for leakage current measurement.
Frequency filter switch to eliminate the effect of harmonics.
Output terminal.

Ø68MAX AC1000Resolution 0.1mA
OUT PUTPEAK 10/100msFilter
2413F
CE
 
AC A
(50/60Hz)
200mA/2/20/200A/1000A
|±1.5%rdg±2dgt (200mA/2/20A)
|±2%rdg±2dgt (200A 0 - 500A)
|±5.5%rdg (501 - 1000A)
AC A
(WIDE)
200mA/2/20/200/1000A
|±1%rdg±2dgt [50/60Hz],
|±3%rdg±2dgt [40Hz - 1kHz] (200mA/2/20A)
|±1.5%rdg±2dgt [50/60Hz],
|±3.5%rdg±2dgt [40Hz - 1kHz] (200A/0 - 500A)
|±5%rdg [50/60Hz],
|±10%rdg [40Hz - 1kHz] (501 - 1000A)
Conductor SizeØ68mm max.
Effect of External
Stray Magnetic Field
Ø15mm 100A
10mA AC max.
Frequency Response40Hz - 1kHz
Output
Waveform :AC200mV against the maximum value of each range (1000A range is 100mV)
Recorder :DC200mV against the maximum value of each range (1000A range is 100mV)
Withstand Voltage3700V AC for 1 minute
Applicable StandardIEC 61010-1 CAT III 300V
IEC 61010-2-032
Power Source6F22 (9V) × 1 *Continuous measuring time: Approx. 60 hours
Dimensions250(L) × 130(W) × 50(D)mm
Weight570g approx.
Accessories9094 (Carrying Case)
6F22 × 1
Instruction Manual
Optional7073 (2WAY Output Cord)